Single Core PVC Flexible Wires

  • Construction : Plain Annealed Flexible Copper Wires (Class-5)
  • Description : Cu/PVC
  • Rated Voltage : 450/750 V
  • Construction/Test Standard : BS:6004,BS EN 50525-2-31,IEC 60228
  • Max. Operating Temp : 70°C
  • Max. Short Cct Temp : 160°C (t≤ 5s)
  • Test Voltage : 2500 V for 5 minutes
  • Fire Propagation Standards : IEC 60332-1-2
  • Minimum Bending Radius (mm) : 3 x d if d ≤ 12 , 4 x d if d > 12
  • Maximum Pulling Tension (N) : 15 x S (S-conductor cross-sectional in mm²) (Recommended not to exceed 1000N)
  • Packing : As per requirement
Area of

Conductor
Insulation

Thickness
Mean Overall Diameter

Lower Limit
Mean Overall Diameter

Upper Limit
Approx. Cable

Weight
DC Resistance

at 20˚C
Current Carrying Capacity

in Conduits at 30o
C (A)
Current Carrying Capacity

in Conduits at 30o
C (A)
mm²mmmmmmkg/kmΩ/km
1 x 1.00.633.41419.513.512
1 x 1.50.72.83.42213.317.515.5
1 x 2.50.83.44.1357.982421
1 x 40.83.94.8504.953228
1 x 60.84.45.3703.34136
1 x 1015.76.81151.915750
1 x 1616.78.11801.217668
1 x 251.28.410.22700.7810189
1 x 351.29.711.73600.554125112
1 x 501.411.513.95000.386151134