Multi Core LSZH Building Wires

  • Construction : Plain Annealed Stranded Copper Wires
  • Description : Cu/LSZH/LSZH
  • Rated Voltage : 600/1000 V
  • Construction/Test Standard : IEC 60502-1,60228,60332-1,60754-1/2,61034
  • Max. Operating Temp : 90°C
  • Max. Short Cct Temp : 250°C (t≤ 5s)
  • Test Voltage : 3500 V for 5 minutes
  • Fire Propagation Standards : IEC 60332-1-2
  • Minimum Bending Radius (mm) : 8 x d (d-cable outer diameter)
  • Maximum Pulling Tension (N) : 15 x S (S-conductor cross-sectional in mm2)
  • Packing : As per requirement
Cores x Area of
Single Conductor
Insulation
Thickness
Sheath
Thickness
Approx. Overall
Diameter
Approx. Cable
Weight
DC Resistance at 20°CCurrent Carrying Capacity
in Conduits at 30°C (A)

2 cables, single-phase
Current Carrying Capacity in Conduits at 30° C (A)

3 or 4 cables, single-phase
mm²mmmmmmkg/kmΩ/kma.c. or d.c.a.c.
2 x 1.50.8
1.810.516512.122
2 x 2.50.81.811.52157.4130
2 x 41.01.813.53104.6140
2 x 61.01.815.04003.0851
2 x 101.01.817.05701.8369
2 x 161.01.819.08151.1591
2 x 251.21.819.010250.727119
3 x 1.50.81.811.5122012.119.5
3 x 2.50.81.812.516357.4126
3 x 41.01.813.522654.6135
3 x 61.01.816.031103.0844
3 x 101.01.818.038551.8360
3 x 161.01.819.57501.1580
3 x 251.21.820.059350.727105
4 x 1.50.81.812.517512.119.5
4 x 2.50.81.813.52457.4126
4 x 41.01.815.03604.6135
4 x 61.01.817.04853.0844
4 x 101.01.819.07001.8360
4 x 161.01.822.010101.1580
4 x 251.21.823.013250.727105

For further information please contact Worldwide Cables engineering department.