Single Core LSZH Building Wires

  • Construction : Plain Annealed Stranded Copper Wires
  • Description : Cu/LSZH
  • Rated Voltage : 450/750 V
  • Construction/Test Standard : BS EN 50525-3,IEC 60228
  • Max. Operating Temp : 90°C
  • Max. Short Cct Temp : 250°C (t≤ 5s)
  • Test Voltage : 2500 V for 5 minutes
  • Fire Propagation Standards : IEC 60332-1-2
  • Minimum Bending Radius (mm) : 9 x d (d-cable outer diameter)
  • Maximum Pulling Tension (N) : 15 x S (S-conductor cross-sectional in mm2)
  • Packing : 90 meter coils or as per requirement
Area of
Conductor
Insulation
Thickness
Approx. Overall
Diameter
Approx. Cable
Weight
DC Resistance at 20°C
Current Carrying Capacity
in Conduits at 30°C (A)

2 cables, single-phase
Current Carrying Capacity
in Conduits at 30°C(A)

3 or 4 cables, single-phase
mm²mmmmkg/kmΩ/kma.c. or d.c.a.c.
1.00.62.651418.11715
1.50.73.12012.12320
2.50.83.8357.413128
40.84.5484.614237
60.85.0653.085448
101.06.51201.837566
161.07.51751.1510088
251.29.02650.727133117
351.210.03500.524164144
501.412.05000.387198175